Fire Alarm Battery Calculator (NFPA 72)

Add up your panel's standby current and alarm current, choose the standby duration your system requires, and get the minimum battery size in amp-hours with the 20% derating most manufacturers specify.

Your numbers

amps

Panel plus all devices at rest. Divide milliamps by 1,000.

amps

Result

Enter your numbers to see the result.

Take this to the job site

The same tools, and more, in apps that work offline when there is no signal.

Fireforge: Fire Alarm Tools

Fireforge: Fire Alarm Tools

NICET/Tools

NAC drop, battery, candela and conduit bending: the fire alarm tech's toolkit, offline.

Fire Alarm Prep: NICET Exam

Fire Alarm Prep: NICET Exam

NICET/Tools

Studying for NICET fire alarm? Fire Alarm Prep has 1,000 questions, mock exams and flashcards, including battery and voltage drop problems like this one.

Read the how-to guides

The formula

Ah = [ (standby amps × standby hours) + (alarm amps × alarm minutes ÷ 60) ] × safety factor

NFPA 72 requires secondary power sized for 24 hours of standby followed by 5 minutes of alarm (15 minutes for voice evacuation systems; 60 hours for some emergency communications and where the AHJ requires). Most manufacturers add 20% to account for battery aging and temperature. Pick the next standard battery size at or above the result: 7, 12, 18, 26, 33 or 55 Ah.

Worked example

0.45 A standby for 24 h is 10.8 Ah. 2.1 A alarm for 5 min is 0.175 Ah. Total 10.975 Ah × 1.2 = 13.17 Ah. Use a 18 Ah battery (or two 7 Ah batteries in parallel is 14 Ah, which also works).

Frequently asked questions

How long must a fire alarm run on battery?

NFPA 72 requires 24 hours of standby followed by 5 minutes of alarm for most systems. Voice evacuation systems need 15 minutes of alarm. Some emergency communications systems require 24 hours standby plus 15 minutes, and certain remote supervising stations need 60 hours.

Why add 20%?

Battery capacity falls with age and cold. A 20% margin is the manufacturer's standard so the system still meets the requirement near end of life.

Where do I get the current numbers?

The panel and device data sheets list standby and alarm current in milliamps. Add them all up.

Related calculators

See all calculators →

Sample exam questions on this topic

Video walkthroughs on YouTube. The TapForge channel posts walkthroughs of these calculators and app demos. Subscribe to the channel.

Get the next tool first.

One short email when a new calculator, guide, practice exam or app goes live. No spam, unsubscribe any time.

You'll get a confirmation email first. We never share addresses.

This calculator gives an estimate for planning and is not tax, legal or engineering advice. Confirm code-related results against the code edition adopted in your jurisdiction and with your authority having jurisdiction, and follow the manufacturer's instructions.