TapForge Studios

HVAC Certification Practice Questions

15 sample questions · 5 topics · based on ASHRAE Handbook, Fundamentals (psychrometrics and refrigeration), NFPA 70 (NEC) fundamentals, Manufacturer charging and setup procedures

This practice exam covers the fundamentals that every HVAC certification tests, from NATE Core and Ready-to-Work to HVAC Excellence and the technical portion of most state licensing exams: the refrigeration cycle, charging by superheat and subcooling, airflow and psychrometrics, control circuits and motors, gas heating and heat pumps.

The questions are based on standard industry practice: ASHRAE psychrometrics, basic refrigeration theory, NEC fundamentals and typical manufacturer procedures. Each session draws ten questions at random from the pool, so run it several times, read the explanations, and use the linked calculators to check the math.

Question of the day

Electrical & controls · October 8

A dual run capacitor in a condensing unit is marked 45/5 µF. Which terminal and value serve the compressor?

Show the answer

C. HERM, 45 µF — The larger section, here 45 µF, is wired to the compressor's start winding through the terminal marked HERM (hermetic); the 5 µF section on FAN serves the condenser fan motor, and C is the common terminal shared by both. Discharge a capacitor before you test it with a meter.

10-question sample

Ten of the 15 sample questions, at random, one at a time, with the explanation after each answer. About five minutes. Full-length timed mock exams are in CoreForge: HVAC Exam Prep.

JavaScript is off, so the sample can't start here; every question is listed further down the page with its answer.

The full exam is in the app

These fifteen are a sample. The app has the complete question bank, full-length timed mock exams that match the real test, flashcards and progress tracking, and it works with no signal.

CoreForge: HVAC Exam Prep

CoreForge: HVAC Exam Prep

NICET/Tools

HVAC certification exam prep: 1,000 questions and mock exams, fully offline.

Airforge: HVAC/R Field Tools

Airforge: HVAC/R Field Tools

NICET/Tools

33 offline HVAC/R tools: P/T charts, superheat, subcooling and diagnosis, ready on the rooftop.

CoolForge: EPA 608 Prep

CoolForge: EPA 608 Prep

NICET/Tools

EPA 608 prep: Core, Type I, II and III, with timed mock exams that work fully offline.

How to study for the HVAC core exam

  1. Draw the refrigeration cycle from memory and label the pressure, temperature and state of the refrigerant at each of the four components.
  2. Memorize the working numbers: 12,000 BTU/h per ton, 400 CFM per ton, 1.08 × CFM × ΔT for sensible heat and 4.5 × CFM × Δh for total heat.
  3. Tie each metering device to its charging method: fixed orifice by superheat, TXV by subcooling, always against the manufacturer's target.
  4. Learn the thermostat letters (R, C, Y, G, W, O/B) and trace what each one switches in the 24-volt circuit.
  5. Make safety automatic: power off and locked out, capacitors discharged, and the meter on the right function before you touch a terminal.

All 15 questions with answers

Open a question to see the answer and the reasoning. Topics: Refrigeration cycle, Superheat & subcooling, Airflow & psychrometrics, Electrical & controls, Gas heat & heat pumps.

1. In which component of a basic vapor-compression system does the refrigerant absorb heat from the air and change from a liquid to a vapor?
  1. Compressor
  2. Condenser
  3. Evaporator
  4. Metering device

Answer: C. The evaporator is the low-pressure, low-temperature coil where liquid refrigerant boils, absorbing heat from the air passing over it. The condenser does the opposite, rejecting heat as the high-pressure vapor condenses back into a liquid.

Topic: Refrigeration cycle

2. What is the state of the refrigerant leaving the compressor through the discharge line in a normally operating system?
  1. Low-pressure, low-temperature vapor
  2. High-pressure, subcooled liquid
  3. Low-pressure mixture of liquid and vapor
  4. High-pressure, high-temperature superheated vapor

Answer: D. The compressor takes in low-pressure superheated vapor from the suction line and discharges high-pressure, high-temperature superheated vapor to the condenser. Subcooled liquid leaves the condenser, and the low-pressure liquid-vapor mixture is what comes out of the metering device into the evaporator.

Topic: Refrigeration cycle

3. What is the job of the metering device in the refrigeration cycle?
  1. Raise the pressure of the vapor leaving the evaporator
  2. Reject heat from the refrigerant to the outdoor air
  3. Drop the liquid's pressure and control flow into the evaporator
  4. Separate oil from the refrigerant before the compressor

Answer: C. The metering device, whether a TXV, fixed orifice or electronic valve, creates the pressure drop between the high and low sides: liquid refrigerant flashes into a cold mixture of liquid and vapor as it enters the evaporator. Raising pressure is the compressor's job and rejecting heat is the condenser's.

Topic: Refrigeration cycle

4. A technician is checking the charge on a split system that uses a fixed-orifice (piston) metering device. Which measurement should be used to judge the charge?
  1. Superheat at the suction line
  2. Subcooling at the liquid line
  3. Compressor amperage only
  4. Discharge line temperature

Answer: A. Fixed-orifice systems are charged by superheat, compared with the manufacturer's chart for the indoor wet-bulb and outdoor dry-bulb conditions. Systems with a thermostatic expansion valve are charged by subcooling, because the TXV keeps adjusting to hold superheat roughly constant no matter how much charge is in the system.

Topic: Superheat & subcooling

5. On a fixed-orifice system the suction pressure converts, on the P/T chart, to a saturation temperature of 40°F. The suction line temperature measured at the evaporator outlet is 52°F. What is the superheat?
  1. 8°F
  2. 12°F
  3. 40°F
  4. 92°F

Answer: B. Superheat is the actual line temperature minus the saturation temperature at the same pressure: 52°F − 40°F = 12°F. Adding the two numbers, or reporting the saturation temperature by itself, are the usual mistakes.

Topic: Superheat & subcooling

6. On a TXV system the manufacturer calls for 10°F of subcooling. Airflow and the coils have been checked and are fine. The liquid-line pressure converts to a 110°F saturation temperature and the liquid line measures 107°F. What is the subcooling, and what should the technician do?
  1. 3°F, undercharged: add refrigerant
  2. 3°F, overcharged: recover refrigerant
  3. 13°F, overcharged: recover refrigerant
  4. 13°F, undercharged: add refrigerant

Answer: A. Subcooling is the condensing saturation temperature minus the liquid line temperature: 110°F − 107°F = 3°F, well under the 10°F target. With airflow and coils already verified, low subcooling on a TXV system means too little refrigerant backed up in the condenser, so add charge slowly while watching subcooling; high subcooling would point to an overcharge.

Topic: Superheat & subcooling

7. What is the usual rule-of-thumb airflow across the indoor coil of a residential air conditioner, per ton of cooling?
  1. 200 CFM per ton
  2. 400 CFM per ton
  3. 600 CFM per ton
  4. 1,200 CFM per ton

Answer: B. About 400 CFM per ton (12,000 BTU/h) is the standard design airflow, so a 3-ton system should move roughly 1,200 CFM. Humid climates often use closer to 350 CFM per ton to remove more moisture, and low airflow shows up in the field as low suction pressure and a frosted coil.

Topic: Airflow & psychrometrics

8. A blower moves 1,000 CFM. Return air enters the evaporator coil at 75°F and supply air leaves at 55°F. Using the sensible heat formula, how much sensible cooling is the coil delivering?
  1. 10,800 BTU/h
  2. 21,600 BTU/h
  3. 43,200 BTU/h
  4. 90,000 BTU/h

Answer: B. Sensible heat in BTU/h = 1.08 × CFM × ΔT = 1.08 × 1,000 × 20 = 21,600 BTU/h. This counts only the temperature change; total heat including moisture removal uses 4.5 × CFM × Δh with the enthalpy change from a psychrometric chart, which is why 90,000 BTU/h (4.5 × 1,000 × 20) is wrong here.

Topic: Airflow & psychrometrics

9. A sling psychrometer reads a dry-bulb temperature of 80°F and a wet-bulb temperature of 80°F. What is the relative humidity of the air?
  1. 0%
  2. 50%
  3. 80%
  4. 100%

Answer: D. The wet bulb is cooled by evaporation, so it reads lower than the dry bulb whenever the air can still absorb moisture. Equal readings mean no evaporation is possible: the air is saturated, relative humidity is 100%, and the dew point equals the dry-bulb temperature.

Topic: Airflow & psychrometrics

10. A dual run capacitor in a condensing unit is marked 45/5 µF. Which terminal and value serve the compressor?
  1. FAN, 5 µF
  2. HERM, 5 µF
  3. HERM, 45 µF
  4. C, 45 µF

Answer: C. The larger section, here 45 µF, is wired to the compressor's start winding through the terminal marked HERM (hermetic); the 5 µF section on FAN serves the condenser fan motor, and C is the common terminal shared by both. Discharge a capacitor before you test it with a meter.

Topic: Electrical & controls

11. On a standard 24-volt residential thermostat, which terminal sends the signal that energizes the cooling contactor coil?
  1. R
  2. G
  3. W
  4. Y

Answer: D. R carries 24 V from the transformer, Y calls for cooling and energizes the contactor coil, G runs the indoor blower, and W calls for heat; C is the common that returns to the transformer. The contactor coil is low-voltage, but its contacts switch line voltage to the compressor and condenser fan.

Topic: Electrical & controls

12. With the thermostat calling for cooling and the contactor coil energized, a technician measures 240 V across one set of contactor contacts (L1 to T1), yet the compressor is not running. What does this reading indicate?
  1. The contacts are closed and carrying current
  2. The 24 V coil is shorted
  3. The run capacitor is weak
  4. The contacts are open or burned and not passing current

Answer: D. Voltage measured across a switch or a set of contacts means the contacts are open: the meter is reading line voltage through the load. Closed, healthy contacts read close to 0 V across them. Since the coil is energized, the contacts themselves are stuck or burned and the contactor should be replaced.

Topic: Electrical & controls

13. A technician is setting up a residential furnace burning natural gas. If the rating plate gave no other value, what manifold pressure would be typical?
  1. 3.5 in. w.c.
  2. 7 in. w.c.
  3. 10.5 in. w.c.
  4. 0.5 psig

Answer: A. Natural gas furnaces typically run a manifold pressure of 3.5 inches of water column, measured at the gas valve outlet with a manometer. Around 7 in. w.c. is a typical supply pressure at the furnace inlet, and 10 to 11 in. w.c. is the usual manifold pressure for LP gas; always set the value shown on the rating plate.

Topic: Gas heat & heat pumps

14. A furnace lights, burns for a few seconds, then shuts the gas off and retries; after three tries it locks out. The igniter glows and the burners ignite every time. What is the most likely cause?
  1. A dirty flame sensor giving a weak rectification signal
  2. A faulty gas valve
  3. Manifold pressure set too high
  4. An open high-limit switch

Answer: A. The furnace proves flame by flame rectification, a tiny DC microamp current that flows through the flame to the sensor; an oxidized sensor or a poor burner ground drops that signal below the control's threshold, so it closes the gas valve even though the burners lit. Clean the sensor and check the microamp reading. An open limit switch would block ignition altogether, and a bad gas valve would not deliver gas on every try.

Topic: Gas heat & heat pumps

15. What does the reversing valve in a heat pump actually do?
  1. Reverses the direction the compressor turns
  2. Bypasses the metering device during the defrost cycle
  3. Redirects refrigerant flow so the coils swap condenser and evaporator roles
  4. Reverses the outdoor fan to melt frost

Answer: C. The four-way reversing valve routes compressor discharge gas either to the outdoor coil (cooling) or to the indoor coil (heating); the compressor always turns the same way. During defrost the valve shifts to cooling mode with the outdoor fan off, so hot gas melts the frost on the outdoor coil while auxiliary heat tempers the supply air.

Topic: Gas heat & heat pumps

Calculators for this exam

Read the how-to guides

Video walkthroughs on YouTube. The TapForge channel posts exam tips and app demos. Subscribe to the channel.

Frequently asked questions

Which exams does this practice test prepare me for?

The fundamentals here appear on NATE Core and Ready-to-Work, the HVAC Excellence employment-ready and professional exams, the technical portion of most state and local HVAC licensing exams, and many employer skills tests. Check the current candidate handbook for the exact outline and question count of the exam you are taking.

What formulas should I memorize?

Superheat is the suction line temperature minus the evaporator saturation temperature, and subcooling is the condensing saturation temperature minus the liquid line temperature. Sensible heat is 1.08 × CFM × ΔT, total heat is 4.5 × CFM × Δh, one ton of cooling is 12,000 BTU/h, and design airflow is about 400 CFM per ton.

Do I still need EPA 608 certification if I pass NATE?

Yes. EPA Section 608 certification is required by federal law for anyone who services, maintains or disposes of equipment containing regulated refrigerants. NATE and HVAC Excellence are voluntary industry certifications, and state or local licensing is separate again, so many technicians end up holding more than one credential.

Other practice questions

All practice questions

Get the next tool first.

One short email when a new calculator, guide, practice exam or app goes live. No spam, unsubscribe any time.

You'll get a confirmation email first. We never share addresses.

These questions were written by TapForge Studios for practice and are not taken from any real exam. They follow the standards and editions named above; the exam you sit may use a different edition, and the certifying body's outline governs. Not a substitute for the code books.