EPA 608 Practice Questions

15 sample questions · 5 topics · based on 40 CFR Part 82 Subpart F, EPA Section 608 regulations (2016 and 2020 updates), AHRI Standard 700 (refrigerant purity)

This free practice exam is for technicians preparing for the EPA Section 608 Technician Certification, the federal credential required to service, maintain or dispose of equipment containing regulated refrigerants. The questions follow the four sections of the real exam: Core, Type I (small appliances), Type II (high-pressure appliances) and Type III (low-pressure chillers).

They are based on 40 CFR Part 82 Subpart F and the EPA Section 608 rules as updated in 2016 and 2020: ozone science, the Montreal Protocol and Clean Air Act, refrigerant classes, recovery, recycling and reclaim rules, cylinder safety, leak rates and the recovery requirements for each appliance type. Each run draws ten questions at random from the pool, so take it more than once and read every explanation.

Question of the day

Type III: low-pressure · October 8

During vapor recovery from a low-pressure chiller, the technician keeps the chilled-water and condenser-water pumps running. What is the purpose?

Show the answer

C. To keep the water in the tubes from freezing — As the remaining refrigerant evaporates it absorbs heat from the water in the chiller tubes, and without flow that water can freeze and split the tubes. Liquid is recovered first, then vapor with the recovery unit's compressor, down to 25 mm Hg absolute with recovery equipment made after November 15, 1993.

10-question sample

Ten of the 15 sample questions, at random, one at a time, with the explanation after each answer. About five minutes. Full-length timed mock exams are in CoolForge: EPA 608 Prep.

JavaScript is off, so the sample can't start here; every question is listed further down the page with its answer.

The full exam is in the app

These fifteen are a sample. The app has the complete question bank, full-length timed mock exams that match the real test, flashcards and progress tracking, and it works with no signal.

CoolForge: EPA 608 Prep

CoolForge: EPA 608 Prep

NICET/Tools

EPA 608 prep: Core, Type I, II and III, with timed mock exams that work fully offline.

Airforge: HVAC/R Field Tools

Airforge: HVAC/R Field Tools

NICET/Tools

33 offline HVAC/R tools: P/T charts, superheat, subcooling and diagnosis, ready on the rooftop.

CoreForge: HVAC Exam Prep

CoreForge: HVAC Exam Prep

NICET/Tools

HVAC certification exam prep: 1,000 questions and mock exams, fully offline.

How to study for the EPA 608 exam

  1. Memorize the numbers the exam keeps coming back to: 80% cylinder fill, 90% and 80% small-appliance recovery, 4 inches Hg, 10 psig test pressure with a 15 psig rupture disc, and 25 mm Hg absolute.
  2. Learn recover, recycle and reclaim as three different things: removing refrigerant, cleaning it on site, and reprocessing it to AHRI 700 at a certified reclaimer.
  3. Know the key dates: venting CFCs and HCFCs was banned in 1992, venting HFC substitutes in 1995, and no new R-22 has been produced or imported since January 1, 2020.
  4. Core is a prerequisite: if you fail it you earn no certification at all, so put most of your study time there before moving to the Type sections.
  5. Practice leak-rate math: pounds added divided by the full charge, annualized, then compared with 20% for commercial refrigeration, 30% for industrial process and 10% for comfort cooling.

All 15 questions with answers

Open a question to see the answer and the reasoning. Topics: Core: regulations, Core: refrigerants & safety, Type I: small appliances, Type II: high-pressure, Type III: low-pressure.

1. Which international agreement commits the United States and other countries to phasing out the production of ozone-depleting refrigerants such as CFCs and HCFCs?
  1. The Montreal Protocol
  2. The Kyoto Protocol
  3. The Clean Air Act
  4. The Paris Agreement

Answer: A. The Montreal Protocol (1987) is the treaty that schedules the phaseout of ozone-depleting substances; the Clean Air Act is the U.S. law that carries it out, and Section 608 of that Act is where the EPA refrigerant rules come from. Kyoto and Paris deal with greenhouse gases, not ozone.

Topic: Core: regulations

2. A technician removes R-22 from a rooftop unit, runs it through the filter-drier on a recycling machine to strip oil, acid and moisture, and later charges it back into equipment owned by the same customer. What has the refrigerant been?
  1. Recovered only
  2. Reclaimed
  3. Purged
  4. Recycled

Answer: D. Recycling means cleaning refrigerant with oil separation and filter-driers so it can go back into the same owner's equipment. Reclaiming means reprocessing it to the AHRI Standard 700 purity specification with a chemical analysis, which only an EPA-certified reclaimer can do; recovery alone is just removing it to a container.

Topic: Core: regulations

3. A contractor recovered 20 pounds of R-22 from a failed condensing unit at one customer's building and wants to use it to top off a different customer's system. Under Section 608, what must happen first?
  1. Nothing, recovered refrigerant may be reused anywhere
  2. It must be recycled on site with a filter-drier
  3. It must be reclaimed to AHRI 700 by a certified reclaimer
  4. It must be relabeled as used refrigerant

Answer: C. Recovered or recycled refrigerant may only go back into equipment belonging to the same owner. When the refrigerant changes ownership it must first be reclaimed to the AHRI Standard 700 specification by an EPA-certified reclaimer, because on-site recycling does not verify purity.

Topic: Core: regulations

4. Which refrigerant family has an ozone depletion potential of zero because its molecules contain no chlorine?
  1. CFCs, such as R-12
  2. HFCs, such as R-134a
  3. HCFCs, such as R-22
  4. Halons, such as Halon 1301

Answer: B. It is the chlorine atom that breaks apart ozone molecules in the stratosphere. HFCs contain only hydrogen, fluorine and carbon, so their ODP is zero, although they are still potent greenhouse gases and may not be vented. CFCs and HCFCs both contain chlorine, and halons contain bromine, which is even harder on ozone.

Topic: Core: refrigerants & safety

5. A refillable recovery cylinder is being filled while sitting on a scale. At what point must the technician stop the transfer?
  1. When the cylinder feels cold to the touch
  2. 60% of its rated capacity
  3. 80% of its rated capacity
  4. 90% of its rated capacity

Answer: C. Recovery cylinders are never filled beyond 80% of their capacity, so the liquid has room to expand if the cylinder warms; an overfilled cylinder can rupture. Weighing is the only reliable way to know the fill level, since temperature and pressure readings do not tell you how much liquid is inside.

Topic: Core: refrigerants & safety

6. A helper suggests pumping recovered refrigerant into an empty disposable cylinder left over from a case of virgin R-410A to save a trip to the shop. What should the technician do?
  1. Agree, if it is filled to no more than 80%
  2. Agree, if the cylinder is evacuated first
  3. Refuse: recovered refrigerant must go straight to a reclaimer
  4. Refuse: disposable cylinders may never be refilled

Answer: D. Disposable (DOT 39) cylinders are built for a single fill of virgin refrigerant; refilling them is prohibited by DOT regulations and dangerous, because they are not designed or tested for repeated pressurization. Recovered refrigerant goes into a DOT-approved refillable recovery cylinder, gray with a yellow top, filled to no more than 80%.

Topic: Core: refrigerants & safety

7. Which of the following meets the Section 608 definition of a small appliance?
  1. A window air conditioner factory-charged with 3 pounds of R-410A
  2. A 4-ton split system holding 8 pounds of R-410A
  3. A walk-in cooler field-charged with 4 pounds of R-404A
  4. A car air conditioner charged with 2 pounds of R-134a

Answer: A. A small appliance is manufactured, charged and hermetically sealed at the factory with 5 pounds or less of refrigerant: refrigerators, freezers, window and room air conditioners, dehumidifiers, vending machines and water coolers. The walk-in cooler is field-assembled, the split system holds more than 5 pounds, and motor vehicle air conditioning falls under Section 609, not 608.

Topic: Type I: small appliances

8. A Type I technician is recovering refrigerant from a vending machine whose compressor runs normally, using EPA-certified recovery equipment. What must the recovery achieve before the sealed system is opened?
  1. 80% of the charge, or 4 inches Hg vacuum
  2. 10 inches Hg vacuum
  3. 0 psig on the compound gauge
  4. 90% of the charge, or 4 inches Hg vacuum

Answer: D. For small appliances the rule is 90% of the charge when the compressor operates, 80% when it does not, or evacuation to 4 inches of mercury vacuum. If the compressor were seized, 80% would be the target, and heating and gently tapping the compressor helps release refrigerant trapped in the oil.

Topic: Type I: small appliances

9. Recovery equipment that has no compressor of its own and relies on the pressure or the compressor of the appliance being serviced is classified as what?
  1. System-dependent (passive) equipment
  2. Self-contained (active) equipment
  3. Push-pull equipment
  4. Vapor-compression equipment

Answer: A. System-dependent, or passive, recovery equipment captures refrigerant using the appliance's own compressor or internal pressure, often into a non-pressurized container, and may only be used on appliances holding 15 pounds or less. Self-contained equipment has its own pump or compressor and can recover from any size of system.

Topic: Type I: small appliances

10. Under the EPA Section 608 leak repair rule as amended in 2016 (thresholds in effect since 2019), an appliance holding 50 pounds or more of ozone-depleting refrigerant must be repaired when its annualized leak rate reaches what level for commercial refrigeration?
  1. 10%
  2. 15%
  3. 20%
  4. 30%

Answer: C. The 2016 amendments set the thresholds at 20% for commercial refrigeration, 30% for industrial process refrigeration and 10% for comfort cooling and all other appliances, replacing the older 35% and 15% figures. A leak over the threshold must normally be repaired within 30 days and the repair verified.

Topic: Type II: high-pressure

11. A comfort-cooling chiller has a full charge of 200 pounds of R-22. Over the past 12 months the technician has added a total of 25 pounds. What is the annualized leak rate, and what does it mean under the leak repair rule?
  1. 5%, below the threshold
  2. 12.5%, above the 10% comfort-cooling threshold
  3. 12.5%, below the 15% comfort-cooling threshold
  4. 25%, above the 20% threshold

Answer: B. 25 lb ÷ 200 lb = 12.5% over 12 months, which exceeds the 10% threshold for comfort cooling under the 2016 rule, so the leak must be repaired within 30 days and the repair proven with verification tests. 15% was the comfort-cooling threshold under the older rule, and 20% applies to commercial refrigeration.

Topic: Type II: high-pressure

12. Which repair is classified as a "major repair" under Section 608, so the appliance must be evacuated to the full prescribed vacuum level rather than only to 0 psig before it is opened?
  1. Replacing a liquid-line filter-drier
  2. Replacing a thermostatic expansion valve
  3. Replacing a Schrader valve core
  4. Replacing the condenser coil

Answer: D. A major repair is one that involves removing the compressor, condenser, evaporator or an auxiliary heat-exchanger coil, and before it the system must be pulled down to the vacuum level in the EPA table for its refrigerant and size. For a non-major repair such as a filter-drier or valve change, evacuating to 0 psig before opening is sufficient.

Topic: Type II: high-pressure

13. Why are low-pressure centrifugal chillers fitted with a purge unit?
  1. To remove air and moisture that leak into the vacuum side
  2. To separate oil carried over into the condenser
  3. To keep the rupture disc from opening at start-up
  4. To reduce the charge during a pump-down

Answer: A. Low-pressure refrigerants such as R-123 boil above 50°F at atmospheric pressure, so the evaporator runs below atmospheric pressure and a leak lets air and moisture in rather than refrigerant out. The purge unit collects these non-condensables from the top of the condenser, and a purge that runs more often than usual is a sign of a leak.

Topic: Type III: low-pressure

14. To find a leak, a technician is raising the pressure in an R-123 chiller by circulating controlled hot water through the tubes. What is the maximum pressure that may be used for the test?
  1. 5 psig
  2. 10 psig
  3. 15 psig
  4. 25 psig

Answer: B. Low-pressure chillers must never be pressurized above 10 psig for leak testing, because the rupture disc that protects the vessel is set to open at 15 psig. Controlled hot water or heating blankets raise the pressure gently; dry nitrogen may also be used, but the same 10 psig limit applies.

Topic: Type III: low-pressure

15. During vapor recovery from a low-pressure chiller, the technician keeps the chilled-water and condenser-water pumps running. What is the purpose?
  1. To raise the head pressure and speed recovery
  2. To return oil to the compressor sump
  3. To keep the water in the tubes from freezing
  4. To keep the purge unit from cycling

Answer: C. As the remaining refrigerant evaporates it absorbs heat from the water in the chiller tubes, and without flow that water can freeze and split the tubes. Liquid is recovered first, then vapor with the recovery unit's compressor, down to 25 mm Hg absolute with recovery equipment made after November 15, 1993.

Topic: Type III: low-pressure

Calculators for this exam

Video walkthroughs on YouTube. The TapForge channel posts exam tips and app demos. Subscribe to the channel.

Frequently asked questions

How is the EPA 608 exam structured?

There are four sections, Core, Type I, Type II and Type III, with 25 multiple-choice questions each. You must pass Core plus at least one Type section, and passing all three Types earns Universal certification. A proctored section is passed with 18 of 25 correct (72%).

Does EPA 608 certification expire?

No. Section 608 certification does not expire and EPA has no renewal requirement, although some employers and states ask for continuing education on their own. Keep a copy of your card, because suppliers must verify certification before selling regulated refrigerants.

Which certification type do I need?

Type I covers small appliances that are factory-sealed with 5 pounds or less of refrigerant. Type II covers high-pressure equipment such as residential and commercial air conditioning, heat pumps and supermarket refrigeration. Type III covers low-pressure chillers, and Universal covers all three. Motor vehicle air conditioning needs a separate Section 609 certification.