Three-Phase Power Calculator (kW, kVA, Amps)

Find the current, apparent power (kVA) and real power (kW) of a motor or load from its voltage, power factor and efficiency, or work back from the amps you measured.

Your numbers

V
A
kW
kVA
%

Use 100% for non-motor loads. For motors, shaft output = input kW x efficiency.

Result

Enter your numbers to see the result.

Take this to the job site

The same tools, and more, in apps that work offline when there is no signal.

Voltbox: Electrician Toolbox

Voltbox: Electrician Toolbox

NICET/Tools

Wire, breaker and conduit calculators plus a full multimeter guide, all offline, so they work in a basement or a mechanical room with no signal.

VoltPrep Electrician Exam Prep

VoltPrep Electrician Exam Prep

NICET/Tools

1,000 practice questions for the journeyman and master electrician exams, with the code-based reasoning behind each answer.

The formulas

  • Three phase: kVA = √3 × V × I ÷ 1000; kW = kVA × PF
  • Single phase: kVA = V × I ÷ 1000; kW = kVA × PF

Going the other way, I = kVA × 1000 ÷ (√3 × V) for three phase. Efficiency converts electrical input to mechanical output on motors.

Worked example

50 A at 480 V three phase and 0.85 power factor: kVA = 1.732 × 480 × 50 ÷ 1000 = 41.6 kVA, kW = 35.3 kW.

Frequently asked questions

What power factor should I use?

Use the nameplate value if it is there. Lightly loaded induction motors run around 0.7 to 0.85; resistive heaters are 1.0.

Does this give the breaker size?

No. Breaker and wire sizing for motors follow NEC Article 430. Use the wire size calculator for general loads.