Sprinkler K-Factor Calculator (Flow and Pressure)
The discharge of a sprinkler follows Q = K × √P. Fill in two values and leave the third blank to find flow in GPM, pressure in psi or the K-factor.
Your numbers
Result
Enter your numbers to see the result.
Take this to the job site
The same tools, and more, in apps that work offline when there is no signal.
Flowforge: Fire Sprinkler Kit
NICET/ToolsSprinkler fitter calculators: K-factor, friction loss, flow test and more, offline.
Fire Sprinkler ITM Prep: NICET
NICET/ToolsNFPA 25 inspection, testing and maintenance prep with real-length NICET mock exams.
The formulas
- Q = K × √P
- P = (Q ÷ K)²
- K = Q ÷ √P
K is the sprinkler's discharge coefficient. A standard 1/2 in. orifice sprinkler is K 5.6. A sprinkler needs a minimum pressure to operate, commonly 7 psi for standard-response, 7 psi for K 5.6 and higher for large-orifice or ESFR. Check the listing for the actual minimum.
Worked example
A K 5.6 sprinkler at 7 psi flows 5.6 × √7 = 14.8 GPM. At 50 psi the same head flows 39.6 GPM.
Frequently asked questions
What is the usual K-factor?
K 5.6 is the standard 1/2 inch orifice. K 8.0 is a large orifice, and K 11.2 and above are used for extended coverage and storage protection.
What is the minimum pressure?
NFPA 13 sets the minimum design pressure by the sprinkler's listing. A common value for standard spray sprinklers is 7 psi, but extended coverage and ESFR sprinklers have higher minimums.