Box Fill Calculator (NEC 314.16)
Count the conductors entering the box by size, add the clamps, fittings, device yokes and grounding conductors, and get the minimum box volume in cubic inches under NEC 314.16(B). The calculator lists the standard metal boxes from Table 314.16(A) that fit, and checks a box volume you enter.
Your numbers
Result
Enter your numbers to see the result.
Take this to the job site
The same tools, and more, in apps that work offline when there is no signal.
Voltbox: Electrician Toolbox
NICET/ToolsVoltBox carries box fill, conduit fill, wire size and voltage drop in one offline app, so you can size the box from the attic.
VoltPrep Electrician Exam Prep
NICET/Tools1,000 practice questions for the journeyman and master electrician exams, with the code-based reasoning behind each answer.
BuildSmith: Construction Calc
NICET/Tools37 trade calculators, code tables and converters for the whole job site, fast and offline.
How the volume is counted (NEC 314.16(B))
- Conductors: each conductor that enters the box and is spliced or terminated, or passes through unbroken, counts once at the volume in Table 314.16(B): 14 AWG 2.00 in³, 12 AWG 2.25, 10 AWG 2.50, 8 AWG 3.00, 6 AWG 5.00. A pigtail or jumper that never leaves the box is not counted.
- Clamps: one allowance of the largest conductor present if the box has one or more internal cable clamps.
- Support fittings: one allowance of the largest conductor for each type of luminaire stud or hickey.
- Devices: two allowances of the largest conductor for each yoke or strap (a switch, receptacle or combination device).
- Grounds: one allowance based on the largest equipment grounding conductor or bonding jumper in the box.
The total is the minimum volume the box must provide. For metal boxes the volume comes from Table 314.16(A); for nonmetallic boxes it is marked inside. Plaster rings, extension rings and domed covers that are marked with a volume add to it.
Worked example
Three 12-2 NM cables (six 12 AWG conductors plus their grounds) enter a box with internal clamps and feed one receptacle. Conductors: 6 × 2.25 = 13.50 in³. Clamps: 2.25. One yoke: 2 × 2.25 = 4.50. Grounds: 2.25. Minimum volume = 22.50 in³. A 3 × 2 × 3-1/2 in. device box (18.0 in³) is too small; the smallest standard box is a 4-11/16 × 1-1/4 in. square (25.5 in³), and a 4 × 2-1/8 in. square (30.3 in³) also works.
Frequently asked questions
Do I count the ground wires?
Yes, but only once for all of them: one allowance based on the largest equipment grounding conductor in the box. The 2020 and later editions add a quarter allowance for each grounding conductor beyond four, which this calculator does not add, so include it yourself on boxes with many cables.
Does a wire that passes through count?
Yes. A conductor that passes through the box without a splice counts once, the same as one that ends in the box. If it is looped or coiled with at least twice the 6 in. of free conductor required by 300.14, it counts twice.
Do I count pigtails and wire nuts?
No. Pigtails, jumpers and splice connectors that stay inside the box are not counted. Neither are the fixture wires from a luminaire canopy in most cases (see the exception in 314.16(B)(1)).
What about a dimmer or GFCI that is bigger than a normal device?
Under 314.16 it still counts as two conductor allowances per yoke, but recent editions count a device wider than a single 2 in. device box as two allowances for each gang it needs. Deep devices are a good reason to pick the next bigger box.
What volume does a plastic box have?
Nonmetallic boxes must be marked with their volume in cubic inches. Use that number in the box volume field; the Table 314.16(A) list is for standard metal boxes only.
Related calculators
Sample exam questions on this topic
Video walkthroughs on YouTube. The TapForge channel posts walkthroughs of these calculators and app demos. Subscribe to the channel.
Get the next tool first.
One short email when a new calculator, guide, practice exam or app goes live. No spam, unsubscribe any time.
You'll get a confirmation email first. We never share addresses.
This calculator gives an estimate for planning and is not tax, legal or engineering advice. Confirm code-related results against the code edition adopted in your jurisdiction and with your authority having jurisdiction, and follow the manufacturer's instructions.